The SeaMetrics AO55 is
a blind (non-indicating)4-20 mA transmitter, designed for use with
almost all SeaMetrics flow sensors. It accepts a pulse frequency input
from the flow sensor, and converts this input into a continuous analog
output signal. Power for the transmitter is taken from the current loop
itself, so only two wires are required. The digital design makes it
possible to span the unit in the field without tools. The
frequency at which 20 mA is desired is entered on a set of rotary
switches, and an internal micro controller automatically scales
all other values accordingly. An additional benefit of the micro
controller is its ability to average inputs, for smoothing of the output
signal. The degree of averaging can be selected in the field, from 2 to
16 seconds. |