Line Items: 0 Total Items: 0 Sub Total: $0.00 |
|
CURRENT
SHOPPING
CART STATUS
▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪▪
Applicable Tax and Freight Charge will be added to Final Invoice.
|
|
|
|
|
|
Single Phase Under Voltage
Monitor/Relay |
|
 |
Trip Points
-
UOA120ALA
-
Drop Out: 97-130 VAC
-
Pick Up: 102-135 VAC
-
Hysteresis: 5 volts
-
UOA240ALA
-
Drop Out: 205-250 VAC
-
Pick Up: 215-260 VAC
-
Hysteresis: 10 Volts

UOA Series
Spec Sheet and Wiring Diagram |
| |
|
RELAY OVERVIEW

The UOA Series offers protection to single phase equipment that is
required to operate above a certain voltage minimum. With
operating voltage applied above the preset Pick-Up voltage, the internal
relay will energize. When the voltage falls below the preset
Drop-Out voltage for a period longer than the release delay, the output
relay will de-energize.
When line conditions return above the
preset Pick-Up voltage, the UOA Series automatically resets and the
internal relay energizes. The Hysteresis in each unit provides a
differential between the Pick-Up and Drop-Out Trip Points. |
| |
|
PURCHASE RELAY
 |
|
ITEM NUMBER |
DESCRIPTION |
PRICE |
|
|
120 VAC Under
Voltage Monitor |
|
|
|
240 VAC Under
Voltage Monitor |
|
|
|
8-Pin Socket
Base |
|
RELAY SPECIFICATIONS
 |
| Relay |
DPDT, 5A @ 240 VAC, Resistive
211 VA @ 240, Inductive |
| Response Times |
Operate: 50 mSEC (approximately)
Release: 0.5 SEC (approximately) |
| Temperature Rating |
Operate: 30 to 131 degrees F
(0-55 C)
Storeage: -49 to 185 degrees F (-45 to 85 C) |
| Power Required |
Models up to 110 VDC: 3 Watts,
Max
Models up to 300 VAC: 5 VA, Max |
| Terminations: |
8-Pin Industrial Plug-in |
| Dimensions |
3.5" H x 2.8" W x 1.75" D |
|
|
|
|